| Model |
3KSS60400/50400 |
| Capacity |
3KVA/2.1kW |
| Input |
| Voltage |
120 or 220V *see note |
| Voltage Range |
120V -15%/+20% or 220V -15%/+20% |
Current
Requirement |
220V - 15.7A @ Full Load (23.5A @ Current limit) |
| 120V - 28.75A @ Full Load (43.1A @ Current limit) |
| Frequency |
50Hz or 60Hz |
| Phase |
Single |
| Output |
| Voltage |
120V (Locked) |
| Voltage Regulation |
±1% |
| Frequency |
400Hz
(50/60hz available) |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% at 100% linear load |
| Output Waveform |
Pure Sinewave |
| Output Current @.7pf |
220V - 13.6A |
| 120V - 25A |
| Non-linear Peak Current for 30 sec. |
220V - 20.4A |
| 120V - 37.5A |
| Power Factor |
0.7 |
| Efficiency |
| AC to AC |
>85% |
| Overload Capacity |
110% continuous,110-150% load 30 seconds, over
150% causes unit to shut down. Auto restart upon removal of
the overload. |
| Short Circuit |
Unit will cut off and must be manually restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB |
| Over Temperature |
Inverter auto cut-off when heat sink temp over
80ºC |
| Audible Alarm |
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, Input & Output voltage - frequency,
loading % |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
-10-50%ºC; 14-122ºF |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 45dB (at 1 meter) |
| Physical |
| Net Weight |
144lbs/64.8kg |
| Width |
7 1/8in/18.1cm |
| Depth |
21 3/8in/54.3cm |
| Height |
19 3/8in/49.35cm |
| Note: Input voltages of 208V single phase
(phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines
and 240V single phase (from a 120/20V split-phase source) -
2 hot lines are both acceptable with one hot on the input N
ternimal, and another hot on the L2 input terminal. |