| Model |
3KSS6050/5060 |
| Capacity |
3KVA/2.1kW Input Current Requirement @ 220V,
16A-120V, 30A |
| Input |
| Voltage |
120 or 220V |
| Voltage Range |
120V-15%/+20% or 220V-15%/+20% |
Current
Requirement |
220V - 15.7A @ Full Load (23.5A @ Current limit) |
| 120V - 28.75A @ Full Load (43.1A @ Current limit) |
| Frequency |
Any Frequency from 45 65 hz (specify if 400hz) |
| Phase |
Single |
| Output |
| Voltage |
120 or 220Vac ±20% Adjustable from nominal |
| Voltage Regulation |
±1% From setpoint |
| Frequency |
50Hz or 60Hz (Switch selectable) (400
Hz available) |
| Frequency Regulation |
±.0005 Hz |
| Harmonic Distortion |
< 3% at 100% Linear Load |
| Output Waveform |
Pure Sinewave |
| Output Current @.7pf |
220V - 13.6A |
| 120V - 25A |
| Non-linear Peak Current for 30 sec. |
220V - 20.4A |
| 120V - 37.5A |
| Power Factor |
0.7 |
| Efficiency |
|
| AC to AC |
>85% |
| Protection |
|
| Overload Capacity |
110% continuous, 110-150% load 30 seconds, over
150% causes unit to shut down. Auto restart upon removal of
overload. |
| Short Circuit |
Unit will cut out and must be manually restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB |
| Over Temperature |
Inverter auto cut-off when heat sink temp. over
80° C |
| Audible Alarm |
|
| Overload |
Sounds continuously |
| Converter Fault |
Sounds continuously |
| Indicator |
|
| LCD |
Converter status, INPUT & OUTPUT voltage-frequency,
loading % |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
|
| Operation Temp. |
-10 to 50° C; 14-122° F |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
< 45dB |
| Physical |
|
| Net Weight |
150lbs/67kg |
| Dimension |
|
| Depth |
21.5in/55cm |
| Width |
7.5in/19cm |
| Height |
19.5in/49cm |
Specifications subject to change without notice. |
Print This Page
|
|