| Model |
5KSS 6050/5060 |
| Capacity |
5KVA/4KW |
| Input |
| Voltage |
120 or 220V-15%/+20% |
| Voltage Range |
-15%/+20% |
Current
Requirement |
220V - 26.1A @ Full Load (39.2A @ Current limit) |
| 120V - 47.9A @ Full Load (71.9A @ Current limit) |
| Frequency |
Any Frequency from 45 65 hz (specify if 400hz) |
| Phase |
Single |
| Output |
| Voltage |
120 or 220Vac ±20% Adjustable from nominal |
| Voltage Regulation |
±1% From setpoint |
| Frequency |
50Hz or 60Hz (Switch selectable) (400Hz
available) |
| Frequency Regulation |
±0.0005Hz |
| Harmonic Distortion |
< 3% at 100% Linear Load |
| Output Waveform |
Pure Sinewave |
| Output Current @ .8pf |
220V - 22.7A |
| 120V - 41.7A |
| Overload@150% for 30 seconds |
220V - 34.1A |
| 120V - 61.5A |
| Efficiency |
|
| AC to AC |
>85% |
| Power Factor |
0.8 |
| Crest Factor |
3:1 |
| Indicator-Detachable & Remote
Control |
| LCD |
Automatically configures to monitor voltage,
frequency, and loading, simultaneously. |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Audible Alarm |
|
| Overload |
Continuously beeping |
| Fault |
Continuously beeping |
| Protection |
|
| Overload |
150% Delay 30 seconds, current limited |
| Short Circuit |
Current limited and cut-off, fuse and breaker |
| EMI Filter |
10-100KHz at 40dB; 100KHz-100MHz at 70dB |
| Over Temperature |
Inverter auto cut-off when heat sink temp. over
80 ° C |
| Dimension |
|
| Depth |
22.9in/68.2cm |
| Width |
9.63in/24.5cmcm |
| Height |
27.75in/70.5cm |
| Environment |
|
| Operation Temperature |
0-40° C; 32-104° F |
| Relative Humidity |
20-90% (non-condensing) |
| Noise Level |
< 58dB (at 1 meter) |
| Weight |
|
| LBS/KG |
232lbs/105.5kg on wheels |
Specifications subject to change without notice. |
Print This Page
|
|