| Model |
6.25KSS60400/50400 |
| Capacity |
6.25KVA/5KW |
| Input |
| Voltage |
120V or 220V *see note |
| Voltage Range |
-15%/+20% |
Current
Requirement |
220V - 32.7A @ Full Load (49A @ Current
limit) |
| 120V - 59.9A @ Full Load (90A @ Current
limit) |
| Frequency |
50Hz or 60Hz ±5% |
| Phase |
Single |
| Output |
| Voltage |
120V (Locked) |
| Voltage Regulation |
±1% |
| Frequency |
400Hz
(50/60hz available) |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% (100% linear load.) |
| Output Waveform |
Pure Sinewave |
| Output Current @ .8pf |
220V - 28A |
| 120V - 52.1A |
| Overload@150% for 30 seconds |
220V - 42A |
| 120V - 78.2A |
| Efficiency |
| AC to AC |
>85% |
| Power Factor |
0.8 |
| Crest Ratio |
3:1 |
| Indicator- Detachable& Remote
Control |
| LCD |
Automatically configures to monitor voltage,
frequency and loading, simultaneously. |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Audible Alarm |
| Overload |
Continuously beeping |
| Fault |
Continuously beeping |
| Protection |
| Overload |
150% delay 30 seconds, current limited |
| Short Circuit |
Current limited cut-off, fuse and breaker |
| EMI filter |
10-100KHz at 40dB; 100KHz-100MHz at 70dB |
| Over Temperature |
Inverter auto cut-off when heatsink temp. over
80ºC |
| Dimension |
| Depth |
22.9in/58cm |
| Width |
9.63in/24.5cm |
| Height |
27.75in/70.5cm |
| Environment |
| Operation Temperature |
-10 to 50° C; 14-122° F |
| Relative Humidity |
20-90% (non-condensing) |
| Noise Level |
< 58dB (at 1 meter) |
| Weight |
| LBS/KG |
232lbs/105.5kg (on wheels) |
| Note: Input voltages of 208V single phase
(phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines
and 240V single phase (from a 120/20V split-phase source) -
2 hot lines are both acceptable with one hot on the input N
ternimal, and another hot on the L2 input terminal. |