| Model |
8KSS60400/50400 |
| Capacity |
8KVA/6.4KW |
| Input |
| Voltage |
220V -15%/+20% *see note |
Current
Requirement |
220V - 41.8A @ Full Load (62.7A @ Current limit) |
| 120V - 76.7A @ Full Load (115A @ Current limit) |
| Frequency |
50Hz or 60Hz ±5% |
| Phase |
Single |
| Output |
| Voltage |
120V (Locked) |
| Voltage Regulation |
±1% |
| Frequency |
400Hz
(50/60hz available)
|
| Output Waveform |
Pure Sinewave |
| Frequency Regulation |
±0.016Hz (Xtal oscillator) |
| Harmonic Distortion |
<3% (100% linear load.) |
| Output Waveform |
Pure Sinewave |
| Output Current @ .8pf |
220V - 36.4A |
| 115V - 66.7A |
Overload@150%
for 30 seconds |
220V - 54.6A |
| 120V - 100.1A |
| Efficiency |
| AC to AC |
>85% |
| Power Factor |
0.8 |
| Crest Ratio |
3:1 |
| Protection |
| Overload |
150% 30Sec cutoff (Current Limited) |
| Overload Capacity |
100% continuous,110-150% load 30 seconds, over
150% causes unit to shut down. Auto restart upon removal of
the overload. |
| Short Circuit |
Unit will cut off and must be manually restarted |
| EMI Filter |
10-100KHz at 40dB, 100KHz-100MHz at 70dB |
| Audible Alarm |
| Overload |
Sounds continuously |
| Fault |
Sounds continuously |
| Indicator |
| LCD |
Converter status, O/P voltage, O/P frequency,
O/P Power |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
| OperationTemp. |
0-40° C; 32-104° F |
| Relative Humidity |
20-90% non-condensing |
| Audible Noise |
Less than 72dB (at 1 meter) |
| Physical |
| Input |
Terminal Block |
| Output |
Terminal Block (Worldwide outlets available) |
| Net Weight |
366lbs/166.4kg |
| Width |
18.9in/48cm |
| Depth |
13.6in/34.5cm |
| Height |
34in/86.4cm |
| Note: Input voltages of 208V single phase
(phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines
and 240V single phase (from a 120/20V split-phase source) -
2 hot lines are both acceptable with one hot on the input N
ternimal, and another hot on the L2 input terminal. |