| Model |
8KSS 6050/5060 |
| Capacity |
8KVA/6.4KW |
| Input |
| Voltage |
120 or 220V-15%/+20% |
Current
Requirement |
220V - 41.8A @ Full Load (62.7A @ Current limit) |
| 120V - 76.7A @ Full Load (115A @ Current limit) |
| Frequency |
Any Frequency from 45 65 hz (specify if
400hz) |
| Phase |
Single |
| Output |
| Voltage |
120 or 220Vac ±20% Adjustable from nominal |
| Voltage Regulation |
±1% From setpoint |
| Frequency |
50Hz or 60Hz (Switch selectable) (400
Hz available) |
| Voltage Regulation |
±1% |
| Frequency Stability |
±0.0005Hz |
| Transient Response |
± 3% (100% Load Variance) No load to full
load with full
recovery within 5 cycles |
| Waveform |
Sinewave THD < 3% at 0-100% linear
load |
| Output Current @ .8pf |
220V - 36.4A |
| 120V - 66.7A |
Overload@150%
for 30 seconds |
220V - 54.6A |
| 120V - 100.1A |
| Efficiency |
|
| AC to AC |
>85% |
| Power Factor |
0.8 |
| Crest Ratio |
3:1 |
| Protection |
|
| Overload |
150% 30 second cut off (Current Limited) |
| Overload Capacity |
110% continuous, 110-150% load 30 seconds,
over 150%
causes unit to shut down. Auto restart upon removal of the
overload. |
| Short Circuit |
Unit will cut-off and must be manually
restarted |
| EMI Filter |
10-100KHz at 40dB; 100KHz-100MHz at 70dB |
| Audible Alarm |
|
| Overload |
Sounds continuously |
| Fault |
Sounds continuously |
| Indicator |
|
| LCD |
Converter status, I/P & O/P voltage,
I/P & O/P frequency |
| LED |
| Line: Green LED |
Inverter: Green LED |
| Fault: Red LED |
Overload: Yellow LED |
|
| Environment |
|
| Operation Temperature |
0-40° C; 32-104° F |
| Relative Humidity |
20-90% (non-condensing) |
| Audible Noise |
< 58dB (at 1 meter) |
| Physical |
|
| Input |
Terminal Block |
| Output |
Terminal Block (worldwide outlets available) |
| Net Weight |
366lbs/166.4kg |
| Width |
18.9in/48cm |
| Depth |
13.6in/34.5cm |
| Height |
34in/88.64 on wheels |
Specifications subject to change without notice. |