10KVA Solid State Frequency Converter Specifications 400hz

Model 10KSS60400/50400
Capacity 10KVA/8KW
Input
Voltage 220V -15%/+20% *see note
Current
Requirement
220V - 52.3A @ Full Load (78.4A @ Current limit)
120V - 95.8A @ Full Load (143.8A @ Current limit)
Frequency 50Hz or 60Hz ±5%
Phase Single
Output
Voltage 120V (Locked)
Frequency 400Hz
Voltage Regulation ±1%
Frequency Stability ±0.016Hz (Xtal oscillator)
Transient Response ±3% (100% load variation.)
No load to full load with full recovery within 5 cycles
Waveform Sinewave THD <3% at 0-100% linear load
Output Current @.8PF 220V - 45.4A
120V - 83.3A
Overload@150%
for 30 seconds
220V - 68.2A
120V - 125A
Efficiency
AC to AC >85%
Power Factor 0.8
Crest Ratio 3:1
Protection
Overload 150% 30Sec cutoff (Current Limited)
Overload Capacity 100% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload.
Short Circuit Unit will cut off and must be manually restarted
EMI Filter 10-100KHz at 40dB, 100KHz-100MHz at 70dB
Audible Alarm
Overload Sounds continuously
Fault Sounds continuously
Indicator
LCD Converter status, O/P voltage, O/P frequency, O/P Power
LED
Line: Green LED Inverter: Green LED
Fault: Red LED Overload: Yellow LED
Environment
OperationTemp. 0-40%ºC; 14-122ºF
Relative Humidity 20-90% non-condensing
Audible Noise Less than 72dB (at 1 meter)
Physical
Input Terminal Block
Output Terminal Block (Worldwide outlets available)
Net Weight 366lbs/166.4kg
Width 18.9in/48cm
Depth 13.6in/34.5cm
Height 34in/86.4cm
Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines and 240V single phase (from a 120/20V split-phase source) - 2 hot lines are both acceptable with one hot on the input N terminal, and another hot on the L2 input terminal.

Specifications subject to change without notice.