| Phase |
3-Phase Input / 3-Phase
Output (*1 phase input / 3 phase output available to 60KVA) |
| Model
Size |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
240KVA |
300KVA |
320KVA |
| INPUT |
| INPUT VOLTAGE (Specify) |
208VY / 380VY / 400VY /
415VY or 220V / 380V / 460V |
| INPUT RANGE |
All above are nominal input
voltages, and can vary ±20% |
| INPUT FREQUENCY |
50 / 60 Hz ±7% |
| POWER WALK IN |
0% - 100% : 20 SECONDS |
| OUTPUT |
| OUTPUT VOLTAGE (Specify) |
208VY / 380VY / 400VY /
415VY or 220V / 380V / 460V |
| For most applications, we reccommend 120/208V
wye (±10%) 4 wire, which includes the aircraft standard
115/200V |
| All above are nominal output voltages,
and adjustable by potentiometer by ±10% |
| VOLTAGE REGULATION |
±1% of settings |
| WAVEFORM |
SINEWAVE |
| OUTPUT POWER FACTOR |
0.8 |
| OUTPUT FREQUENCY (Specify) |
400 Hz ± 0.1 Hz |
PHASE SHIFT UNDER 100%
UNBALANCE LOAD |
<0.5º |
| THD (LINEAR LOAD) |
<2% |
| OVERLOAD |
<100% |
CONTINUOUS |
| 110-125% |
15 MINUTES |
| 125-150% |
10 MINUTES |
| >150% |
1 MINUTE |
| OVERALL
CHARACTERISTICS |
| Model
Size |
10KVA |
20KVA |
30KVA |
40KVA |
50KVA |
60KVA |
80KVA |
100KVA |
120KVA |
160KVA |
200KVA |
240KVA |
300KVA |
320KVA |
| OVERAL EFFICIENCY |
90% |
91% |
91% |
91.5% |
92% |
92% |
92.5% |
93% |
93% |
93% |
93% |
95% |
95% |
95% |
MAXIMUM HEAT
DISSIPATION (KW) |
1.1 |
1.3 |
1.9 |
2.6 |
3 |
3.5 |
4.6 |
5.4 |
6.5 |
8.7 |
8.7 |
6.5 |
6.5 |
6.5 |
| DIMENSIONS (H x W x D) mm / in |
1450 x 550 x 1000
58 x 22 x 40 |
1600 X 1100 X 1000
63 x 43 x 40 |
1600 X 2200 X 1000
63 X 86 X 40 |
| WGT. KG/lbs |
250 / 551 |
280 / 617 |
380 / 839 |
450 / 992 |
520 / 1146 |
630 / 1389 |
770 / 1698 |
900 / 1984 |
1100 / 2425 |
1350 / 2976 |
2300 / 5071 |
2500 / 5512 |
2800 / 6173 |
2900 / 6393 |
| AUDIBLE NOISE @ 1m |
<65 dBA |