HomeAbout Us Contact Us Site Map
Solid State Frequency ConverterRotary Frequency ConverterLine Isolation

Electrocon Frequency Converters

60 to 50 Hz · 50 to 60 Hz · 60 to 60 Hz Isolation · 50/60 to 400 Hz

12KVA Solid State Frequency Converter Specifications 400Hz

 
Model 12KSS60400/50400
Capacity 12KVA/8.4KW
Electrical Input
Voltage 220V -15%/+20% *see note
Frequency 50Hz or 60Hz ±5%
Electrical Output
Voltage 120Vac self-regulated 100A
Frequency 400Hz
Voltage Regulation ±1%
Frequency Stability ±0.016Hz (Xtal oscillator)
Transient Response ±3% (100% load variation.)
No load to full load with full recovery within 5 cycles
Waveform Sinewave THD <3% at 0-100% linear load
Overload Capacity 110% continuous,110-150% load 30 seconds, over 150% causes unit to shut down. Auto restart upon removal of the overload.
Power Factor 0.8
Crest Ratio 3:1
Efficiency
AC to AC >85%
Protection
Overload 150% 30Sec cutoff (Current Limited)
Short Circuit Unit will cut off and must be manually restarted
EMI Filter 10-100KHz at 40dB, 100KHz-100MHz at 70dB
Audible Alarm
Overload Sounds continuously
Fault Sounds continuously
Indicator
LCD Converter status, O/P voltage, O/P frequency, O/P Power
LED
Line: Green LED Inverter: Green LED
Fault: Red LED Overload: Yellow LED
Environment
OperationTemp. -10-50%ºC; 14-122ºF
Relative Humidity 20-90% non-condensing
Audible Noise Less than 72dB (at 1 meter)
Physical
Input Terminal Block
Output Terminal Block (Worldwide outlets available)
Net Weight 366lbs/166.4kg
Width 18.9in/48cm
Depth 13.6in/34.5cm
Height 34in/86.4cm
Note: Input voltages of 208V single phase (phase-to-phase on a 3-phase 120/208V line)- with 2 hot lines and 240V single phase (from a 120/20V split-phase source) - 2 hot lines are both acceptable with one hot on the input N ternimal, and another hot on the L2 input terminal.

1Specifications subject to change without notice.

Questions?


Please contact us using the form HERE